FP-GFirefighting Systems
Gas suppression systems: FM-200, Novec 1230 and CO2
We design gas suppression for rooms where water won't do: server rooms, electrical switchrooms, archives and control rooms. We calculate the agent quantity for the room, install the cylinders, pipework, nozzles and release panel, test the room's integrity before handover, and maintain the system afterwards.

At a glance
- Provided by
- Osool Al-Salama Fire Systems & Contracting, an engineering company in Al Khobar since 2011
- Where
- The Eastern Province: Al Khobar, Dammam, Dhahran, Jubail and Al Ahsa, from our office in Al Khobar
- For
- Server rooms and data centres, electrical and generator rooms, control and telecom rooms, archives and museums, laboratories
The agents and where each one fits
FM-200HFC-227ea
A clean agent that leaves no residue and doesn't conduct electricity, suitable for normally occupied rooms within design limits. HFCs are being phased down in many countries.
Novec 1230FK-5-1-12
A clean agent with a very low climate impact, stored as a liquid that vaporises on discharge. Novec is a 3M trade name; the chemical itself is FK-5-1-12.
Carbon dioxideCO₂
Effective and inexpensive, but its extinguishing concentration is dangerous to people, so it's used in normally unoccupied spaces such as generator rooms and some industrial equipment, with a warning and time delay before discharge.
Room integrity testDoor fan test
The agent works at a set concentration that has to stay in the room long enough. The test measures the room's leakage and checks the concentration will hold, before handover and after any change to the room.
What governs the design
- 01
Clean agent systems are designed to NFPA 2001, which covers the design concentration, discharge time and how long the agent must be held in the room.
NFPA 2001: Standard on Clean Agent Fire Extinguishing Systems - 02
CO2 systems have their own standard, NFPA 12, including the measures that protect people before discharge.
NFPA 12: Standard on Carbon Dioxide Extinguishing Systems - 03
The Saudi Fire Code SBC 801 covers alternative automatic extinguishing systems and refers to NFPA standards for them; what your site needs is set by the approved design and Civil Defense.
الكود السعودي للحماية من الحرائق SBC 801 - 04
3M, the owner of the Novec brand, announced it would exit PFAS manufacturing by the end of 2025. So at supply time we confirm with you which source of FK-5-1-12 is available and listed for the system.
3M: 3M to Exit PFAS Manufacturing by the End of 2025 (20 Dec 2022)
03What we provide
- A room survey: volume, openings, equipment, false ceiling and raised floor
- Agent quantity, nozzle layout and pipework calculated to the standard
- Cylinders, release panel, detectors, alarms and the pre-discharge delay supplied
- Installation and interfacing with the fire alarm, with HVAC shut-down on release
- Room integrity test, commissioning and handover with drawings
- Periodic inspection and refilling under the annual maintenance contract
Inspection and upkeep
Common practice under NFPA 2001; what your site needs is set by Civil Defense and the manufacturer:
- Agent quantity and cylinder pressure checked at least twice a year.
- A yearly inspection of the whole system: panel, detectors, alarms and release devices.
- Room integrity reviewed yearly and after any change: a new opening, new services or different doors.
- Recharge after any discharge, and cylinder testing at the intervals the standard sets.
Questions about this service
Related guides
What's the difference between FM-200 and Novec 1230?
Both are clean agents that leave no residue and don't harm equipment. FM-200 (HFC-227ea) is the more established, but it is an HFC being phased down in many countries; Novec 1230 (FK-5-1-12) has a very low climate impact, but its supply changed after 3M's exit from PFAS manufacturing. The choice depends on the room, availability and listings, and we explain it in our proposal.
Is the gas dangerous for staff?
Clean agents such as FM-200 and FK-5-1-12 are designed for normally occupied rooms within limits set by the standard; even so, the system sounds an alarm and gives time to leave before discharge. CO2 is dangerous at extinguishing concentration, so it's used in unoccupied spaces with extra safeguards.
Does the gas damage servers and equipment?
No. A clean agent doesn't conduct electricity and leaves no residue or water, which is why it's chosen for server, electrical and archive rooms instead of water sprinklers.
Why does the room need an integrity test?
Because the agent works at a set concentration that must stay in the room long enough. If the room leaks through openings or around doors, the concentration drops too soon. The test measures the leakage, and we seal the openings before handover.
I have an existing gas system — can you inspect and refill it?
Yes. Refilling and inspecting gas systems is part of our maintenance scope. We inspect the system, tell you its condition and what it needs, and add it to a maintenance contract if you wish.
Let's start with what your facility needs
Send your request and one of our engineers will contact you to discuss the facility and the right systems, then arrange the site survey and quote with you.